柔性直流换流站空气净距研究
Study on Air Clearance of Voltage Source Converter Station
-
摘要: 为了确保柔性直流换流站电气布置的合理性与安全运行,需要确定合理的空气净距取值,作为换流站的设计依据。本文详细介绍了基于g参数法的换流站空气净距计算原理及方法,探讨了海拔高度在2 000 m以内的大气修正方法。文章以"大型风电场柔性直流输电接入技术研究与开发"示范工程+160 kV换流站为例,采用g参数法进行最小空气净距计算,仿真计算出最苛刻的运行环境条件,为大气环境修正提供依据和输入,得出了换流站的空气净距计算方法和工程间隙取值。Abstract: To ensure rationality of voltage source converter station layout and operational safety, reasonable air clearance is needed as design basis. G parameter method is adopted to calculate the minimum air clearance, and atmospheric correction is discussed when altitude is below 2 000 m. +160 kV converter station for large-scale wind plant integrated with power system based on VSC technology demonstration project is used as an example to analyze air clearance calculating method using g parameter method. The harshest operating condition is calculated by simulation as input of atmospheric correction, and actual air clearance for design is determined.