Study on Air Clearance of Voltage Source Converter Station
doi: 10.16516/j.gedi.issn2095-8676.2015.S1.011
- Received Date: 2015-11-01
-
Key words:
- air clearance /
- g parameter method /
- voltage source converter /
- atmospheric correction
Abstract: To ensure rationality of voltage source converter station layout and operational safety, reasonable air clearance is needed as design basis. G parameter method is adopted to calculate the minimum air clearance, and atmospheric correction is discussed when altitude is below 2 000 m. +160 kV converter station for large-scale wind plant integrated with power system based on VSC technology demonstration project is used as an example to analyze air clearance calculating method using g parameter method. The harshest operating condition is calculated by simulation as input of atmospheric correction, and actual air clearance for design is determined.
Citation: | GUO Jinchuan, ZHOU Min, KONG Zhida, CHEN Li. Study on Air Clearance of Voltage Source Converter Station[J]. SOUTHERN ENERGY CONSTRUCTION, 2015, 2(S1): 50-54. doi: 10.16516/j.gedi.issn2095-8676.2015.S1.011 |