Shichao HAN, Jiaming ZHAO, Cuiyun WANG, Bin ZHAO. Design Improvement of Steam Generator Blowdown System[J]. SOUTHERN ENERGY CONSTRUCTION, 2016, 3(3): 45-47,53. doi: 10.16516/j.gedi.issn2095-8676.2016.03.009
Citation:
|
Shichao HAN, Jiaming ZHAO, Cuiyun WANG, Bin ZHAO. Design Improvement of Steam Generator Blowdown System[J]. SOUTHERN ENERGY CONSTRUCTION, 2016, 3(3): 45-47,53. doi: 10.16516/j.gedi.issn2095-8676.2016.03.009
|
Design Improvement of Steam Generator Blowdown System
- 1.
Zhengzhou Branch, China Nuclear Power Engineering Co., Ltd., Zhengzhou 450052, China
- 2.
China Nuclear Power Engineering Co., Ltd., Beijing 100840, China
- Received Date: 2015-10-28
- Publish Date:
2020-07-17
-
Abstract
According to the results of the full range of accident analysis, in case of steam generator tube rupture, in order to make affected SG water level will not rise too fast, and need to control the affected SG water level and pressure by steam generator blowdown system. According to design improvement of steam generator blowdown system, increase the system design bases, the blowdowns are routed to the IRWST inside the containment, in order to depressurize affected SG pressure and control affected SG level, to prevent the affected steam generator is filled with water, meet the requirements of steam generator blowdown system in the design basis accident under the safety function. The improvement design can satisfy the third generation nuclear power technology, provide theoretical basis for the safety of the third generation nuclear power in China.
-
References
[1]
|
中国核电工程有限公司. 蒸汽发生器排污系统手册(CP03XTTBXTS02) [M]. 北京:CNPE,2015. |
[2]
|
中国核电工程有限公司. 运行技术规范(0426XOTSYXB03) [M].北京:CNPE, 2011. |
[3]
|
张往锁,曹夏昕. 非能动余热排除系统敏感性分析[J]. 原子能科学技术,2013, 47(3): 409-415.
ZHANG W S, CAO X X. Sensitivity analysis of passive residual heat removal system[J]. Atomic Energy Science and Technology, 2013, 47(3): 409-415. |
-
-