LIN Rui, HUANG Xudan, XIAO Huanhui. VFTO Calculation and Analysis of the New Interconnecting Transformer in a Nuclear Power Station[J]. SOUTHERN ENERGY CONSTRUCTION, 2016, 3(S1): 55-60. doi: 10.16516/j.gedi.issn2095-8676.2016.S1.013
Citation: LIN Rui, HUANG Xudan, XIAO Huanhui. VFTO Calculation and Analysis of the New Interconnecting Transformer in a Nuclear Power Station[J]. SOUTHERN ENERGY CONSTRUCTION, 2016, 3(S1): 55-60. doi: 10.16516/j.gedi.issn2095-8676.2016.S1.013

VFTO Calculation and Analysis of the New Interconnecting Transformer in a Nuclear Power Station

doi: 10.16516/j.gedi.issn2095-8676.2016.S1.013
  • Received Date: 2016-11-07
  • Publish Date: 2020-07-17
  • One Nuclear Power Station No. 3 Unit reconstruction project has improved the transformer design due to No. 1&2 Units had ever suffered failures of the interconnecting transformer coil by VFTO, so the new No.3 interconnecting transformer should be fully considered the impact of VFTO to avoid the similar incidents. This article analyzed 10 routine operations about the VFTO impact to the equipment by using the ATP electromagnetic transient calculation program. The results shown that the overvoltage value near isolating switch is the highest, which is 2.95 p.u., the maximum overvoltage at the transformer entrance is 1.60 p.u., the insulation level of the equipment could fulfill the requirement of VFTO.
  • 通讯作者: 陈斌, bchen63@163.com
    • 1. 

      沈阳化工大学材料科学与工程学院 沈阳 110142

    1. 本站搜索
    2. 百度学术搜索
    3. 万方数据库搜索
    4. CNKI搜索

Article Metrics

Article views(286) PDF downloads(136) Cited by()

Related

VFTO Calculation and Analysis of the New Interconnecting Transformer in a Nuclear Power Station

doi: 10.16516/j.gedi.issn2095-8676.2016.S1.013

Abstract: One Nuclear Power Station No. 3 Unit reconstruction project has improved the transformer design due to No. 1&2 Units had ever suffered failures of the interconnecting transformer coil by VFTO, so the new No.3 interconnecting transformer should be fully considered the impact of VFTO to avoid the similar incidents. This article analyzed 10 routine operations about the VFTO impact to the equipment by using the ATP electromagnetic transient calculation program. The results shown that the overvoltage value near isolating switch is the highest, which is 2.95 p.u., the maximum overvoltage at the transformer entrance is 1.60 p.u., the insulation level of the equipment could fulfill the requirement of VFTO.

LIN Rui, HUANG Xudan, XIAO Huanhui. VFTO Calculation and Analysis of the New Interconnecting Transformer in a Nuclear Power Station[J]. SOUTHERN ENERGY CONSTRUCTION, 2016, 3(S1): 55-60. doi: 10.16516/j.gedi.issn2095-8676.2016.S1.013